Walk-trough. Configuring ICONICS9 Awx32Log for redundant DB logging.

Note! Must have redundancy license.

Step 1. Awx32Server configured for 2 digital alarms using OPC Simulator.

Step 2. Subscription successfully tested in OPC Data Spy, by writing to Out1 and Out2 values.

Step 3. Primary SQL2005 AwxLog2 db configured using OLEDB as Primary data source.

Step 4. Secondary SQL2005 AwxLog1 db (on the same server) configured using OLEDB as Redundant data source.

Step 5. Only Primary AwxLog2 receives updates.

Step 6. TraceWorx reports 1 INSERT per change of state in alarm, db not defined, only table.